Structured cabling: What is the maximum allowed length for horizontal cabling from the telecommunications closet (TC) to the wall outlet, excluding patch cords?
-
A90 meters
-
B3 meters
-
C6 meters
-
D300 meters
-
ENone of the above
Answer
Correct Answer: 90 meters
Explanation
Introduction / Context:Telecommunications standards (such as TIA/EIA-568) define channel and component lengths for structured cabling systems. The 'horizontal link' connects the telecommunications closet to the work area outlet and has a strict maximum to preserve performance at rated categories.
Given Data / Assumptions:
- We are discussing the permanent horizontal cabling segment (solid conductor) from TC to outlet.
- Patch cords at the closet and the workstation are additional components.
- Copper twisted-pair cabling standards are assumed.
Concept / Approach:The standard channel length is typically 100 meters total = 90 meters horizontal + up to 10 meters of patch cords. The permanent link (horizontal) itself must not exceed 90 meters to ensure that insertion loss, crosstalk, and delay parameters remain within specification for the overall 100-meter channel.
Step-by-Step Solution:
Identify component limits: permanent link vs. patch cords.Recall the standard total channel length of 100 m.Subtract typical patch allowance (up to 10 m) to get 90 m for horizontal.Select '90 meters' as the correct maximum for the horizontal run.Verification / Alternative check:Review structured cabling guidelines: many design documents explicitly state 90 m permanent link plus 10 m patch cords.
Why Other Options Are Wrong:
- 3 m and 6 m are typical patch cord lengths, not horizontal run limits.
- 300 m far exceeds copper Ethernet standards and would violate attenuation limits.
- None of the above is incorrect since 90 m is correct.
Common Pitfalls:Confusing total channel length (100 m) with the horizontal-only limit (90 m). Designers must budget patch length accordingly.
Final Answer:90 meters