Refrigeration performance from energy flows: A condenser rejects 120 kW of heat while the compressor consumes 30 kW of shaft power. What is the coefficient of performance (COP) of the refrigeration system?

Mechanical Engineering Heat Transfer, Refrigeration and Air Conditioning Difficulty: Easy
Choose an option
  • A
    1/4
  • B
    1/3
  • C
    3
  • D
    4
  • E
    2

Answer

Correct Answer: 3

Explanation

Introduction / Context:The coefficient of performance (COP) of a refrigerator measures how much cooling effect is obtained per unit of input work. Interpreting heat rejection and compressor power correctly is fundamental for energy audits and sizing.

Given Data / Assumptions:

  • Heat rejected at condenser, Q_H = 120 kW.
  • Compressor power input, W = 30 kW.
  • Steady-state operation with Q_H = Q_L + W.

Concept / Approach:For a refrigerator, COP_R = Q_L / W, where Q_L is the cooling (evaporator) load. Since the condenser rejects the sum of the evaporator load and compressor work, we find Q_L by subtraction.

Step-by-Step Solution:

Compute evaporator load: Q_L = Q_H − W = 120 − 30 = 90 kW.Compute COP: COP_R = Q_L / W = 90 / 30 = 3.Therefore, COP = 3.

Verification / Alternative check:The energy balance must hold: Q_H = 120 kW = 90 kW + 30 kW, which is satisfied. Typical COP values of 2–5 are realistic for many systems, so 3 is plausible.

Why Other Options Are Wrong:

1/4 and 1/3 invert the ratio; they would correspond to W > Q_L, which contradicts the data.4 would require Q_L = 120 kW with W = 30 kW, but Q_L is only 90 kW here.2 would imply Q_L = 60 kW, not matching the balance.

Common Pitfalls:Mistaking the condenser heat flow Q_H for the cooling load Q_L. Always subtract compressor work to find Q_L from Q_H.

Final Answer:

3

Discussion & Comments
No comments yet. Be the first to comment!
Join Discussion